Maxking

BMS Temperature Sensors

Maxking Limited

BMS Temperature Sensors

BMS temperature sensors are used throughout Building Management Systems (BMS) and HVAC installations to measure temperature and allow the control system to monitor and regulate heating, cooling and ventilation equipment.

How they work

A temperature sensor measures the temperature of air, water, pipework or another medium and provides a signal to the BMS controller. The controller converts that signal into a temperature value, such as 21.5°C, which can then be displayed, logged or used within control logic.

Common sensor types include NTC thermistors, PT100, PT1000, and active transmitters providing 0–10 V or 4–20 mA signals.

Common BMS temperature sensors

SensorTypical application
Room sensorMeasures room/space temperature
Duct sensorSupply, extract, return and outside-air ducts
Immersion sensorHeating and chilled-water pipework using a pocket
Strap-on sensorMeasures pipe surface temperature
Outside-air sensorExternal temperature measurement
Frost sensorProtects coils and equipment from freezing
Average temperature sensorMeasures temperature across a larger duct or coil
Remote probe sensorRefrigeration, plant and specialist applications

Passive vs active sensors

Passive sensors change their electrical resistance according to temperature. The BMS controller measures the resistance and converts it to °C. Common examples are 10K3A1, 10K4A1, 20K NTC, PT100 and PT1000.

Active sensors/transmitters contain electronics that convert the temperature measurement into a standard signal, commonly 0–10 V or 4–20 mA. These are particularly useful where longer cable runs or standardised analogue signals are required.

Example – 10K3A1

A 10K3A1 thermistor has a nominal resistance of approximately 10,000 Ω at 25°C.

As an NTC sensor:

Temperature rises → resistance falls
Temperature falls → resistance rises

The BMS uses the appropriate resistance/temperature curve to calculate the actual temperature.

Why temperature sensors matter

Accurate sensing allows a BMS to control boilers, chillers, AHUs, pumps, valves, heating circuits, fan coils and ventilation systems. The readings can also be used for alarms, frost protection, energy optimisation, trend logging and fault diagnosis.

One important point when replacing a BMS sensor is that physical appearance isn’t enough. The replacement must have the correct sensing characteristic—such as 10K3A1, PT1000 or 4–20 mA—and the BMS input must be configured for that same signal type.

The specification of a 10K3A1 temperature sensor

A 10K3A1 temperature sensor is a 10 kΩ NTC thermistor commonly used in HVAC/BMS applications. The designation generally refers to the 10K Type 3 / 3A1 thermistor curve.

Specification 10K3A1
Sensor type NTC thermistor
Nominal resistance 10,000 Ω at 25°C (77°F)
Resistance characteristic Resistance decreases as temperature increases
Nominal Beta (β) value ≈ 3976 K
Common designation 10K Type 3 / 10K3A1
Reference temperature 25°C
Typical operating range Approximately −40°C to +125°C, depending on sensor construction
Typical accuracy Usually ±0.2°C to ±0.5°C around normal HVAC temperatures, depending on the manufacturer
BMS input Passive resistive / thermistor input
Polarity None

 

Typical 10K3A1 resistance values

Approximate values useful for BMS commissioning and fault finding are:

Temperature Approx. Resistance
−20°C 96.8 kΩ
−10°C 55.3 kΩ
0°C 32.6 kΩ
5°C 25.4 kΩ
10°C 19.9 kΩ
15°C 15.7 kΩ
20°C 12.5 kΩ
25°C 10.0 kΩ
30°C 8.06 kΩ
35°C 6.53 kΩ
40°C 5.33 kΩ
50°C 3.60 kΩ
60°C 2.49 kΩ
70°C 1.76 kΩ
80°C 1.27 kΩ
90°C 0.93 kΩ
100°C 0.70 kΩ

 

For Tridium Niagara N4

For an N4 controller/input configured for a 10K3A1 thermistor, the important characteristics are:

R25 = 10,000 Ω
Beta ≈ 3976 K

One important point: 10K thermistors are not interchangeable just because they all measure 10 kΩ at 25°C. A 10K Type 2, Type 3/3A1 and other 10K curves can produce significantly different temperatures away from 25°C. For a BMS specification, I would therefore specify “10 kΩ NTC, Type 3/3A1 characteristic, R25 = 10 kΩ” rather than simply “10K thermistor.”

hvacproducts.co.uk bms-temperature-sensors bms-temperature-sensors

 

Below is the full 10K3A1 resistance/temperature table from −40°C to +120°C in 1°C increments, calculated using:

hvacproducts.co.uk bms-temperature-sensors bms-temperature-sensors

Temp °C Resistance Ω Temp °C Resistance Ω
-40 411,749 41 5,070
-39 382,827 42 4,871
-38 356,157 43 4,680
-37 331,548 44 4,498
-36 308,825 45 4,324
-35 287,832 46 4,158
-34 268,423 47 4,000
-33 250,469 48 3,848
-32 233,850 49 3,703
-31 218,457 50 3,564
-30 204,192 51 3,431
-29 190,964 52 3,304
-28 178,691 53 3,183
-27 167,297 54 3,066
-26 156,712 55 2,955
-25 146,875 56 2,848
-24 137,727 57 2,746
-23 129,215 58 2,648
-22 121,291 59 2,554
-21 113,910 60 2,463
-20 107,031 61 2,377
-19 100,617 62 2,294
-18 94,633 63 2,215
-17 89,048 64 2,138
-16 83,831 65 2,065
-15 78,958 66 1,995
-14 74,402 67 1,927
-13 70,141 68 1,862
-12 66,154 69 1,800
-11 62,421 70 1,740
-10 58,925 71 1,682
-9 55,649 72 1,627
-8 52,578 73 1,574
-7 49,698 74 1,522
-6 46,995 75 1,473
-5 44,458 76 1,426
-4 42,075 77 1,380
-3 39,836 78 1,336
-2 37,731 79 1,294
-1 35,752 80 1,253
0 33,890 81 1,214
1 32,138 82 1,176
2 30,487 83 1,140
3 28,933 84 1,105
4 27,468 85 1,071
5 26,088 86 1,038
6 24,785 87 1,007
7 23,557 88 977
8 22,397 89 947
9 21,302 90 919
10 20,268 91 892
11 19,291 92 866
12 18,367 93 840
13 17,493 94 816
14 16,667 95 792
15 15,885 96 769
16 15,145 97 747
17 14,444 98 726
18 13,780 99 705
19 13,151 100 685
20 12,554 101 666
21 11,988 102 648
22 11,452 103 630
23 10,942 104 612
24 10,459 105 595
25 10,000 106 579
26 9,564 107 563
27 9,150 108 548
28 8,756 109 533
29 8,382 110 519
30 8,026 111 505
31 7,687 112 492
32 7,365 113 479
33 7,058 114 466
34 6,765 115 454
35 6,487 116 442
36 6,222 117 431
37 5,969 118 420
38 5,728 119 409
39 5,499 120 399
40 5,279    

For Niagara N4 / BMS commissioning, some useful checkpoints from this calculated curve are:

0°C = 33.89 kΩ
10°C = 20.27 kΩ
20°C = 12.55 kΩ
25°C = 10.00 kΩ
30°C = 8.03 kΩ
40°C = 5.28 kΩ
50°C = 3.56 kΩ
60°C = 2.46 kΩ
70°C = 1.74 kΩ
80°C = 1.25 kΩ
90°C = 919 Ω
100°C = 685 Ω

One caution: this is a Beta-equation calculation using β = 3976 K. A manufacturer’s official 10K3A1 thermistor curve may use Steinhart-Hart coefficients or a resistance lookup table, so small differences are possible, especially at the extremes of the temperature range.

Leave a Comment

Scroll to Top